Operating Instructions and Installation Instructions

Page.19
No ACTION Possible problem/cause Solution
6.
NO
Resistance in thermo
current circuit too high.
Check cables and connections in
thermo current circuit.
Magnet unit drops
(audible click)
Not enough heat on
thermocouple.
Check position of pilot to
thermocouple and intensity of pilot
flame.
Motor turns to main gas
and pilot stays lit.
Low voltage from
thermocouple.
Check connections and, if necessary,
replace thermocouple. Do not
overtighten the connections!
Short because
thermocouple end is
damaged.
Replace thermocouple, do not
overtighten the connections!
NO
IGN sequence stops. No
reaction to transmitter
command (receiver does
not react).
Press RESET button, see
instructions.
Add ground wire between pilot
burner and gas valve.
OK
Do not coil the IGN cable.
Shorten IGN cable if possible.
7.
Main burner is lit.
NO
Gas valve manual knob in
“MAN” position.
Turn knob to “ON” position.
OK
8.
Main burner stays lit.
NO
Too much / too little air
flow / draft at pilot, blows
out or is smothered.
Check whether restriction plate has
been correctly applied in unit, see
instructions.
Poor flue location, check correctness
of layout and connections.
OK
9.
Magnet unit drops while
motor turns.
3 beeps
NO
Receiver batteries low. Replace batteries, 1.5V AA quality
alkaline!
System can be switched
OFF via remote control.
NO
System can be
switched OFF via
ON/OFF switch.
NO
Short between TC and SW
cable.
Check connection to interrupter
block.
YES
YES
OK OK
Replace gas valve.