Operating Manual
Accu-Wave Chapter 3 Set up Level, Level Alarms, and Volume
TN Technologies 3-5
Example: Set up Level
Set up level as the primary measurement for a tank. Before beginning the gauge setup, you
need to measure the distance from the Reference Line on the sensor housing to the desired
Zero Level point on the tank and the distance from the Zero Level point to the desired
Maximum Level to be measured. See Figure 3.3.
Figure 3.3 Entries Required to Set up Level as Primary Measurement
Follow the steps in the table below to set up level as the primary measurement using the
example measurements shown in Figure 3.3.
Example: Set up Level as Primary Measurement
Menu Display User Action
Set up level, level
alarms, & volume.↓↓
←←Exit Setup.
Other functions→→
From the measurement display, press → to move to
the “Set up level,...” menu shown at the left.
Then, press ↓ to access the “Set up level,…” menu
items.
General HELP text.→→
Information on how
to set up this gauge
NEXT↓↓
General HELP text for setting up the gauge. Press →
to read the help text, press ↓ to proceed to the next
menu item.
primary measurement:
Distance
Change to Level→→
NEXT↓↓
The default primary measurement is “distance.” Press
the → key to change to “level.” Then press ↓ to
proceed to the next menu item.
Reference Line
Zero Level
Maximum Level
Zero Level
22.5 ft