Operating Manual

Chapter 7 Action Items Accu-Wave
7-4 TN Technologies
Hold Action Items
“Hold Action Items” Menu
Display Comments
“Hold” action items
(Hold reading, etc)
NEXT
Press to enter the “Hold action items” menu. Press
to continue to next “Action Item” menu subgroup.
Clear all holds
(none now in effect)
Exit this menu.
NEXT EXECUTE CMD
Execute this command to clear all holds (if any holds
are in effect).
Hold current output
at max (20.00 mA)
Exit this menu.
NEXT EXECUTE CMD
Holds all current outputs at the value entered for the
maximum current output.
Hold current output
at min (4.000 mA)
Exit this menu.
NEXT EXECUTE CMD
Holds all current outputs at the value entered for the
minimum current output.
Hold current output
at zero mA
Exit this menu.
NEXT EXECUTE CMD
Holds all current outputs at 0.0 mA.
Current output
hold mode value
50.00% of scale
NEXT
Enter value in % for the mid-range current output
hold value. Default value is 50.00%.
Hold current output
at 50.00% of scale
Exit this menu.
NEXT EXECUTE CMD
Press to execute command to hold current output at
the mid-range value specified in the previous menu
item.
Level hold mode
value
0.000 ft level
NEXT
Enter the hold value for the primary measurement
(level or distance). This value is also used as the “lost
echo value” when “go to hold value” is selected as the
“echo loss mode.” See page 5-8.
Hold level at
0.000 ft level
Exit this menu.
NEXT EXECUTE CMD
Press to hold primary measurement value at the
hold value specified in the previous menu item. After
executing command, display changes to read “Clear
holds.” Press to clear the hold level command.