Instruction Manual

Installation and Operation Handbook Programmer Operation
2408 and 2404 Controller 5-13
Segment type
Select the segment type using
or :
rmP.r: Ramp to a new setpoint at a set rate
rmP.t: Ramp to a new setpoint in a set time
dwEl: Dwell for a set time
StEP: Step to a new setpoint
cALL: Call another program as a subroutine
(only available in multi-program controllers)
End: Make this segment the end of the program.
Press
The parameters that follow tYPE’ depend on the type of segment selected as
shown in the table below. The function of each parameters follows the table.
Parameter Segment type selected
rmP.r rmP.t dwEl StEP cALL End
Hb
9 9 9 9
tGt
9 9
9
rAtE
9
dur
9 9
PrG.n
9
cYc.n
9
outn
9 9 9 9
9
SYnc
9 9 9 9
End.t
9
Table 5-3 Parameters that follow segment type
Holdback type
Only appears when Holdback per segment has been selected.
Use or to select:
OFF: Holdback disabled
Lo: Deviation Low Holdback
Hi: Deviation High Holdback
bAnd: Deviation Band Holdback
Press
Target setpoint
Target setpoint for rmP.r’, ‘rmP.torStEP segments.
Set the target setpoint using or .
Press Continued on the next page.