Instruction Manual

Ordering Code Installation and Operation Handbook
A
-4 2416 Controller
-
Hardware
coding
Part 2: Configuration
Sensor input Range min Range max Units Options
K 0 1000 C CF
Notes:
1. PDSIO is a proprietary technique developed by Eurotherm for bi-directional
transmission of analogue and digital data between instruments.
Mode 1: provides logic heating to a Eurotherm TE10S solid state relay with feedback of a
general load fault alarm.
Mode 2: provides logic heating to a Eurotherm TE10S solid state relay with feedback of load
current and two alarms: solid state relay failure and heater circuit failure.
2. Range min and Range max: Thermocouple and RTD sensor inputs will always display
over the full operating range shown in Sensor input table. For these inputs, the values
entered here are the low and high setpoint limits. For process inputs, the values are the
display scaling corresponding to the minimum and maximum input values.
See note 2
Continued
Sensor input Range min &max
Standard sensor inputs
°C °F
J J thermocouple -210 to 1200 -340 to 2192
K K thermocouple -200 to 1372 -325 to 2500
T T thermocouple -200 to 400 -325 to 750
L L thermocouple -200 to 900 -325 to 650
N N thermocouple -250 to 1300 -418 to 2370
R Type R - Pt13%Ph/Pt -50 to 1768 -58 to 3200
S Type S - Pt10%Rh/Pt -50 to 1768 -58 to 3200
B Type B - Pt30%Rh/Pt6%Rh 0 to 1820 32 to 3308
P Platinel II 0 to 1369 32 to 2496
C *Type C W5%Re/W26%Re
(Hoskins)*
0 to 2319 32 to 4200
Z RTD/PT100 -200 to 850 -325 to 1562
Process inputs
F -9.99 to + 80mV 0 to 9999
Y 0-20 mA Linear 0 to 9999
A 4-20 mA Linear 0 to 9999
W 0-5V DC Linear 0 to 9999
G 1-5V DC Linear 0 to 9999
V 0-10V DC Linear 0 to 9999
Custom Sensor inputs (* replaces type C thermocouple)
D Type D - W3%Re/W25%Re 0 to 2399 32 to 4350
E E thermocouple -270 to 1000 -450 to 1830
1 Ni/Ni18%Mo 0 to 1399 32 to 2550
2 Pt20%Rh/Pt40%Rh 0 to 1870 32 to 3398
3 W/W26%Re (Englehard) 0 to 2000 32 to 3632
4 W/W26%Re
(Hoskins)
0 to 2010 32 to 3650
5 W5%Re/W26%Re
(Englehard)
10 to 2300 50 to 4172
6 W5%Re/W26%Re
(Bucose)
0 to 2000 32 to 3632
7 Pt10%Rh/Pt40%Rh 200 to 1800 392 to 3272
Options
Add as many options as required
Control options
NF On/Off control
DP Direct acting PID
control
PD Power feedback
disabled
Cooling options
CF Fan cooling
CW Water cooling
CL Oil cooling
Front panel buttons
MD Auto/man button
disabled
RD Run/hold button
disabled
Programmer options
HD Dwell time in hours
HR Ramp rate in units/hour
(minutes is standard)
Units
C Centigrade
F Fahrenheit
K Kelvin
X Blank