Instruction Manual

Load Current Monitoring and Diagnostics Installation and Operation Handbook
8-6 2416 Controller
8.6 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS
Configuration of PDS load current diagnostics is in four parts:-
1. Configure the Logic Module for PDS Mode 1 or 2 operation.
2. Configure the Low and High Current trip alarms.
3. Attach the alarms to operate an output relay.
4. Set up the Scaling Factor.
First enter Configuration Level. See Chapter 5
8.7 TO CONFIGURE THE LOGIC MODULE FOR PDS MODES 1 OR 2
Do This This Is The Display You Should See Additional Notes
Press until the
1A Conf is
displayed
This opens the
configuration list
associated with
module position 1A
Press to show
id
This shows the
identity of the
module
The module identity
is log
ic output
Press to show
Func
Press
or
to show SSr1 or
SSr 2 as required.
This shows the
func
tion of module
The module function
is set to PDS mode
1
Press to show
VAL.L
Press
or
to show 0.0
This is the lower PID
demand level
To set the minimum
PID signal to 0%
Press to show
VAL.H)
Press
or
to show 100.0
This is the upper
PID demand level
To set the maximum
PID signal to 100%
1A
Conf
id
Log
VAL.H
100.0
VAL.L
0.0
Func
SSr1