Installation and Operation Handbook Load Current Monitoring and Diagnostics
2416 Controller 8-5
8.3 TO SET THE ALARM TRIP LEVELS
Do This This Is The Display You Should See Additional Notes
From the HOME
display (Figure 2.3)
press
until the
AL LiSt is
displayed
To select the Alarm
List header
Press button
until the desired
alarm number is
displayed
Press
or
to adjust the alarm
trip level
To select the
diagnostic alarm
parameter found
under the Alarm List
header
The alarm trip level
is set to 123
8.4 SHORT CIRCUIT SSR ALARM AND HEATER FAIL ALARM
These alarms exist as Diagnostic Alarms in the controller. To make the alarm active it is
only necessary to turn on the diagnostic alarm feature in the Alarm List in the Operator Level
Do This This Is The Display You Should See Reason
From the HOME
display press
button until the AL
LiSt is displayed
This opens the list
which contains the
diAG mnemonic
Press until
DiAG is displayed
Press
or
to select YES
This activates the
diAG mnemonic to
allow Diagnostic
Alarms to be
displayed in the
lower readout of the
HOME display
8.5 RELAY OUTPUTS
Any plug in module can be used for alarms provided they are not already being used for
another purpose , such as control. Any one or more alarms can be attached to an output,
which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operating
external beacons or audible devices.
AL
LiSt
DiAG
YES
AL
LiSt
1---
123
1 2 3 or 4
indicates the alarm
number;
--- indicates the
alarm type:-
e.g. LCr or HCr