Instruction Manual
Installation and Operation Handbook User Calibration
2416 Controller 7-7
Select High-point Calibration
This is the Calibration Status display, again.
Use
/ to select the parameter for the High-point Calibration
of Input 1, ‘ip1.H’.
Press
Adjust High-point Calibration
This is the display for adjusting the High Calibration point of
Input 1. The lower readout is a live reading of the process value,
which changes as the input changes.
Feed the desired high-point calibration signal to the controller,
from the calibration source. If the lower readout does not show
this value, then use
/ to adjust the reading to the required
value.
Press
to return to the ‘ip-List’ header.
To protect the calibration against unauthorised adjustment return
to Operator level and make sure that the calibration parameters are
hidden. Parameters are hidden using the ‘Edit’ facility
described in Chapter 3.
Adj
1200
CAL
ip1.L