Instruction Manual
Programmer Operation Installation and Operation Handbook
5-12 2416 Controller
Segment type
Select the segment type using
or :
•
rmP.r Ramp to a new setpoint at a set rate
• rmP.t Ramp to a new setpoint in a set time
• dwEl Dwell for a set time
•
StEP Step to a new setpoint
•
cALL Call another program as a subroutine
(only available in 4-program controllers)
•
End Make this segment end of program.
Press
The parameters that follow ‘tYPE’ depend on the type of segment selected.
Parameter Segment type selected
rmP.r rmP.t dwEl StEP cALL End
Hb
9 9 9 9
tGt
9 9
9
rAtE
9
dur
9 9
PrG.n
9
outn
9 9 9 9
9
cYc.n
9
dwEl
9
End.t
9
Pwr
9
Table 5-3 Parameters that follow segment tYPE
Holdback type
[Only appears when Holdback per segment has been selected.]
Use or to select:
• OFF: Holdback disabled
• Lo: Deviation Low Holdback
• Hi: Deviation High Holdback
• bAnd: Deviation Band Holdback
Press
Target setpoint
Target setpoint for ‘rmP.r’, ‘rmP.t’ or ‘StEP’ segments.
Set the target setpoint using
or .
Press
Continued on the next page.
Hb
bAnd
tgt
100
type
rmp.r