Instruction Manual
Understanding the Ordering Code Installation and Operation Handbook
A
-4 2408 and 2404 Controller
-
Hardware
Part 2: Configuration
coding Sensor
input
Range
min
Range
max
Display
Units
Continued next page
K
0 1000
C
See note 4
Sensor input Range min &max
Standard sensor inputs
°C °F
J J thermocouple -210 to 1200 -340 to 2192
K K thermocouple -200 to 1372 -325 to 2500
T T thermocouple -200 to 400 -325 to 750
L L thermocouple -200 to 900 -325 to 650
N N thermocouple -250 to 1300 -418 to 2370
R Type R - Pt13%Ph/Pt -50 to 1768 -58 to 3200
S Type S - Pt10%Rh/Pt -50 to 1768 -58 to 3200
B Type B -
Pt30%Rh/Pt6%Rh
0 to 1820 32 to 3308
P Platinel II 0 to 1369 32 to 2496
Z RTD/PT100 -200 to 850 -325 to 1562
Process inputs
F +/- 100mV 0 to 9999
Y 0-20 mA Linear 0 to 9999
A 4-20 mA Linear 0 to 9999
W 0-5V DC Linear 0 to 9999
G 1-5V DC Linear 0 to 9999
V 0-10V DC Linear 0 to 9999
Factory downloaded input
C *Type C
W5%Re/W26%Re
(Hoskins)*
0 to 2319 32 to 4200
D Type D -
W3%Re/W25%Re
0 to 2399 32 to 4350
E E thermocouple -270 to 1000 -450 to 1830
1 Ni/Ni18%Mo 0 to 1399 32 to 2550
2 Pt20%Rh/Pt40%Rh 0 to 1870 32 to 3398
3 W/W26%Re
(Englehard)
0 to 2000 32 to 3632
4 W/W26%Re
(Hoskins)
0 to 2010 32 to 3650
5 W5%Re/W26%Re
(Englehard)
10 to 2300 50 to 4172
6 W5%Re/W26%Re
(Bucose)
0 to 2000 32 to 3632
7 Pt10%Rh/Pt40%Rh 200 to 1800 392 to 3272
8 Exergen K80 I.R.
pyrometer
-45 to 650 -50 to 1200
Display Units
C Celcius
F Fahrenheit
K Kelvin
X Linear input