Instruction Manual

User Calibration Installation and Operation Handbook
7-2 2408 and 2404 Controller
USER CALIBRATION ENABLE
The User calibration facility must first be enabled in configuration level by setting the
parameter ‘UCAL' in the input conf list to 'YES'. This will make the User calibration
parameters visible in Operator ‘FuLL’ level.
Select configuration level as shown in Chapter 6, Configuration.
+
The Calibration Configuration List
Press until you reach the ‘CAL-Conf’ list.
Press until you reachUCAL’.
User Calibration Enable
Use or to select:
YES: Calibration enable
no: Calibration disabled
Press
and together to go to the Exit display.
Exit configuration
Use
or to select ‘YES’ to return to Operator level.
CAL
UCAL
no