Electrical Installation
Wire sizes recommended by National Electric Code. Minimum wire temperature rating is 90 °C.
Turn off all electricity to the working area at the main breaker panel prior to installation.
1. Have a licensed electrical professional Connect the 240 or 480 VAC Wall receptical
(model dependant) per Local and National Electrical codes. The system uses 4
conductor wire (3 phase and a ground). See wiring diagrams on pg. 15.
Model
Description
Volts
Heaters
X3
kW
Amps
Wire
Fuse
Phase
Room Volume
TSD-600-240
SuperDuty Generator 15 kW, 240V
208/240
5000 W
15 kW
39
6
50
3
600 Cubic Feet
TSD-900-240
SuperDuty Generator 18 kW, 240V
208/240
6000 W
18 kW
47
6
60
3
900 Cubic Feet
TSD-1200-240
SuperDuty Generator 24 kW, 240V
208/240
8000 W
24 kW
63
4
80
3
1200 Cubic Feet
TSD-1600-240
SuperDuty Generator 30 kW, 240V
208/240
10000 W
30 kW
79
2
100
3
1600 Cubic Feet
TSD-600-480
SuperDuty Generator 15 kW, 480V
480
5000 W
15 kW
18
10
25
3
600 Cubic Feet
TSD-900-480
SuperDuty Generator 18 kW, 480V
480
6000 W
18 kW
22
10
30
3
900 Cubic Feet
TSD-1200-480
SuperDuty Generator 24 kW, 480V
480
8000 W
24 kW
29
8
40
3
1200 Cubic Feet
TSD-1600-480
SuperDuty Generator 30 kW, 480V
480
10000 W
30 kW
36
6
50
3
1600 Cubic Feet
Note: All electrical wiring must be done per local electrical codes
and by a licensed electrical professional.
Wall Receptacle
(Included)
Generator size 18Wx21Dx48H