Installation Sheet
4 Electrical Wiring
4'
5'
8'
Installation note
We do not recommend a
ceiling height exceeding
10 feet.
Lowering ceiling
height to 8 feet helps
create a more efcient
steam room.
3
THERMASOL.COM
I
800.776.0711
If you are installing the unit or thinking of adding one on your next project,
you will need to make sure the unit is sized properly.
Calculate the shower area
(Length x Width x Height = Cubic Feet)
and conrm the ceiling height does not exceed 8 feet.
The set of numbers in the generator model number
represents the maximum capacity.
Example: Generator model SSA-240
will be sufcient up to 240 cubic feet
(with a ceiling not exceeding 8 feet in height).
Up-size 1 Unit size for every foot over 8 foot to
a maximum of 10 foot.
Model number can be found on the box or generator.
ThermaSol’s generators can be placed up to 50 feet from the
shower; in an attic, closet or below a sink are ideal locations.
Make sure the walls, ceiling and oor materials are suitable for
use with steam. If using acrylic walls, they must be steam rated
from their manufacturer. ThermaSol only recommends SSA-ACR
generator for acrylic modules.
q Wire cutters or wire strippers
q Adjustable wrench
q Screwdriver (Phillips and regular)
q Solder and ux
q 1-1/8" inch hole saw for ThermaSol
SteamVection steamhead rough-in
q Drill motor
q Propane torch
q 1" socket with ratchet
q Other tools as required
Read warnings on page 2. For illustrative purposes only. Consult with qualied professional for steam room construction details.
The size of the shower will determine the size
of the generator. The size of the generator will
determine electrical requirements.
q All the electrical wiring must be done per
National/Local Electrical Codes.
q Run 240V Power source to the generator.
q Use copper wire only.
q Wire sizes recommended by NEC (2002 Version). Minimum wire
temperature rating 90°C. Type THHN.
q Each generator should be wired to their own separate breaker
q Turn off all electricity to the working area at the main breaker panel!
q Leave power OFF during installation process.
AF Series Generator Installation Instructions
3 Sizing or Double Checking the Unit Specied
MODEL INPUT VOLTAGE KW RATING AMPS PHASE WIRE BREAKER ELECTRICAL MAX. ROOM SIZE
SSA-ACR 208-240VAC 3.5 17 1 10 20 NEMA 6-30P Acrylic Shower
SSA-84 208-240VAC 6.0 28 1 10 30 NEMA 6-30P 84 CU.FT.
SSA-140 208-240VAC 8.0 37 1 8 40 NEMA 6-50P 140 CU.FT.
SSA-240 208-240VAC 10 46 1 8 50 NEMA 6-50P 240 CU.FT.
SSA-395 208-240VAC 11 55 1 6 60 Hardwire 395 CU.FT.
SSA-575 208-240VAC 15 69 1 4 90 Hardwire 575 CU.FT.
ThermaSol requires that a licensed electrician perform all electrical work.