Installation Sheet
1. Use copper or brass ttings only. NEVER USE GALVANIZED FITTINGS OR IRON PIPE!
2. The steam outlet is 1" NPT and requires brass unions.
3. The generator must be upright, accessible, and on a level surface. The access panel (top and front of the unit), must
be unobstructed and allow for easy access.
4. Unit may be installed up to 50 ft. away from the steam room.
5. Do not plumb a trap in the steam line or plumb the pressure relief valve into the steam line. Do not plumb the steam
line (pipe) up, down, then back up again. This will cause a steam trap.
6. If possible, pitch the steam line (pipe) back towards the generator or towards the steam head. Always avoid
perfectly level plumbed lines.
7. Before connecting the water line to the generator, ush the water line into a ve-gallon pail to remove any silt or
other material that may be in the line. IMPORTANT - Not doing so may effect the water delivery to the unit.
THERMASOL.COM
I
800.776.0711
4
Power Pak Series 3 Generator Installation Instructions
4 Installation Requirements
CAUTION
If the unit is run without water, serious damage
may result! This damage is not covered under
ThermaSol’s limited warranty.
Note: Failure to follow specic installation
instructions will cause the warranty to be void.
Generator Dimensions
Read the warnings on page 2. For illustrative purposes only. Consult with a qualied professional for steam room construction details.
16.25
32.00
18.13