Manual

AHP
TTPSales@thermasys.com 262.554.8330 www.thermaltransfer.com
144
AIR COOLED AHP
Electric Motor & Fan Data
Fan Motor Full Load Nema Thermal Approx. Shipping Sound
Model CFM H.P. Voltage Phase Amps Hz RPM Frame Overload Weight (Lbs.) dB(A) at 3 ft
AHP-400
2200
1.0
115/208-230 1 6.0 60 3450
120 97
1825/2200 208-230/460 3 3.6/3.2 50/60 2850/3450
56C
AHP-725
3600
1.5
115/208-230 1 8.5 60 3450
170 100
3025/3600 208-230/460 3 4.8/4.2 50/60 2850/3450
AHP-950 4700
1.5
115/208-230 1 8.6
145TC
330 92
208-230/460 3 4.6
AHP-1200 7000
5.0 230 1 23.0 184TC No
450 94
3.0 208-230/460 3 8.8 182TC
AHP-1600 9700 5.0 208-230/460 13.4 60* 1740 184TC 515 96
AHP-2000 11000 19.6 600 98
AHP-2500 14000
7.5
230/460
3
213TC
625 98
AHP-3000 17500 24.8 645 102
AHP-3500 17500
10.0
215TC
750 102
All motors shown are TEFC. Other motor options available upon request. Published electrical ratings are approximate, and may vary because of motor brand. Actual ratings are
on motor nameplate.
Fan motors must not be cycled. Outdoor applications must be protected from direct weather. If ductwork or additional static resistance is added to the cooler airstream, an
auxiliary air mover may be required.
*3 phase motors available in 50Hz. Reduce performance by 10%.
Recommended Typical Installation
1. Support piping as needed. Flexible connectors must be properly installed
to validate warranty.
2. Coolers should not operate in ambient temperatures below 35°F (1°C).
Consult factory for recommendations.
3. The fan cannot be cycled.
4. AHP coolers operated outdoors must be protected from weather.
Consult factory for recommendations.
5. If ductwork or additional static resistance is added to the cooler airstream,
an auxiliary air mover may be required.