Instructions / Assembly
Requirements
• Use minimum 75 C copper
• Use only code approved, appropriately listed fuse holders and Fuses
Maximum Fuse Rating 30 AMP , 600 Volt
Total Maximum Current Rating 0783-41 / 0786-41 120 AMPS DC
Maximum Fuse Short Circuit Current 10ka
Fuse Holder Torque 13.6 in lb Flat or Phillips Head Driver
Din Rail Mounted Terminal Block Torque 9 - 14 in lb Flat Head Driver
Torque Data* for Box Lug
Wire Size Torque
AWG mm2 in lbs Nm
14-10 2.1-5.3 35 4
8 8.4 40 4.5
6-4 13.3-21.2 45 5.1
2 13.3-21.2 50 5.7
Torque Data* for Negative Power Distribution Block
Wire Size Torque
Screw Driver
External Drive
Wrench
AWG mm2 in lbs Nm
14-10 2.1-5.3 35 75 4
8 8.4 40 75 4.5
6-4 13.3-21.2 45 110 5.1
Main 2/0-14 13.3-21.2 0 120 5.7
Torque Data* for Ground Lug
Wire Size Torque
AWG mm2 in lbs Nm
14-10 2.1-5.3 35 4
8 8.4 40 4.5
6-4 13.3-21.2 45 5.1
2-2/0 13.3-21.2 50 5.7
5