Instructions / Assembly
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS- This manual contains important instructions for models 0783-
41 and 0786-41that shall be followed during installation of the combiner.
SolaDeck models are listed by ETL as PV Combiners under the standard:
UL 1741, First Edition
SolaDeck models meet UL 50 Type 3R rainproof requirements.
This enclosure is rated for up to 600 VDC fuses.
Grounding Instructions- Each system should be connected to a grounded,
permanent wiring system. All system wiring and system grounding must comply with NEC Code,
ANSI/NFPA 70-1996, or other appropriate codes, is the responsibility of the installer.
The equipment ground on SolaDeck is marked with the symbol:
Note: Solar panels produce electrical current when lighting is present, even during
overcast weather. Do not wire from the array to the SolaDeck combiner. Complete all
connections inside the SolaDeck combiner first and then connect the array.
General Wiring Installation Instructions
• Remove any necessary knockouts before securing the SolaDeck to the roof or other
surface.
• Follow the mounting instructions page 3
• Slide the fuse holders onto the Din rail and lock in place.
• Secure the Bus Bar to the fuse holders.
• Install the negative power distribution block using the steel studs in the location
designated for the Negative PV Model (0783).
• Install negative terminal blocks on DIN rail where designated PV Negative and lock in
place. Model (0786).
• Connect all wires to fuse holders, bus bar lug and negative terminals, securing them
according to the listed torque values from table on page 5.
• Conduit and Strain relief fittings and hubs must comply with UL 514B
4