Datasheet
UCD9248
www.ti.com
SLVSA33A –JANUARY 2010–REVISED AUGUST 2012
Table 5. Temperature Sensor Mapping
TEMPERATURE MUX INPUT POWER STAGE
A0 DPWM-1A
A1 DPWM-1B
A2 DPWM-3A
A3 DPWM-2A
A4 DPWM-2B
A5 DPWM-4A
A6 n/c
A7 n/c
Temperature Balancing
Temperature balancing between phases is performed by adjusting the current such that cooler phases draw a
larger share of the current. Temperature balancing occurs slowly (the loop runs at a 10 Hz rate), and only when
the phase currents exceeds the PMBus settable TEMP_BALANCE_IMIN. This minimum current threshold
prevents the controller from "winding up" and forcing one phase to carry all the current under a low-load
condition, when the total current may be insufficient to significantly affect phase temperatures.
Soft Start, Soft Stop Ramp Sequence
The UCD9248 performs soft start and soft stop ramps under closed loop control.
Performing a start or stop ramp or tracking is considered a separate operational mode. The other operational
modes are normal regulation and light load regulation. Each operational mode can be configured to have an
independent loop gain and compensation. Each set of loop gain coefficients is called a "bank" and is configured
using the CLA_GAINS PMBus command.
Start ramps are performed by waiting for the configured start delay TON_DELAY and then ramp the internal
reference toward the commanded reference voltage at the rate specified by the TON_RISE time and
VOUT_COMMAND. The DPWM and SRE outputs are enabled when the internal ramp reference equals the
preexisting voltage (pre-bias) on the output and the calculated DPWM pulse width exceeds the pulse width
specified by DRIVER_MIN_PULSE. This ensures that a constant ramp rate is maintained, and that the ramp is
completed at the same time it would be if there were not a pre-bias condition.
Figure 13 shows the operation of soft-start ramps and soft-stop ramps.
Figure 13. Start and Stop Ramps
Copyright © 2010–2012, Texas Instruments Incorporated Submit Documentation Feedback 25