Datasheet
SDA
SCL
Data Line
Stable
Data Valid
Change
of Data
Allowed
Data Output
by Transmitter
Data Output
by Receiver
SCL from
Master
NACK
Start
Condition
ACK
Clock Pulse for
Acknowledgment
S
1
2
8
9
TPL0401A
TPL0401B
TPL0401C
SLIS144A –SEPTEMBER 2011–REVISED MARCH 2012
www.ti.com
The data byte follows the address ACK. The R/W bit is kept low for transfer from the master to the slave. The
data byte is followed by an ACK sent from this device. Data are output only if complete bytes are received and
acknowledged. The output data is valid at time (tpv) after the low-to-high transition of SCL, during the clock cycle
for the ACK.
On the I
2
C bus, only one data bit is transferred during each clock pulse. The data on the SDA line must remain
stable during the high pulse of the clock period, as changes in the data line at this time are interpreted as control
commands (start or stop) (see Figure 13).
Figure 13. Bit Transfer
A stop condition, a low-to-high transition on the SDA input/output while the SCL input is high, is sent by the
master (see Figure 13).
The number of data bytes transferred between the start and the stop conditions from transmitter to receiver is not
limited. Each byte of eight bits is followed by one ACK bit. The transmitter must release the SDA line before the
receiver can send an ACK bit.
A slave receiver that is addressed must generate an ACK after the reception of each byte. The device that
acknowledges has to pull down the SDA line during the ACK clock pulse so that the SDA line is stable low during
the high pulse of the ACK-related clock period (see Figure 14). Setup and hold times must be taken into account.
Figure 14. Acknowledgement on the I
2
C Bus
10 Submit Documentation Feedback Copyright © 2011–2012, Texas Instruments Incorporated
Product Folder Link(s): TPL0401A TPL0401B TPL0401C