Datasheet

www.ti.com
System Reset Control
Mode Register Reset Control
SPI SERIAL CONTROL PORT FOR MODE CONTROL (PCM1850A)
MSB
0 IDX6 IDX5 IDX4 IDX3 IDX2 IDX1 IDX0 D7 D6 D5 D4 D3 D2 D1 D000
LSB
Register Index (or Address) Register Data
R0001-01
IDX0 D7 D6 D4D5 D3 D2 D1 D0
MS
MC
MD
IDX1IDX2IDX3IDX4IDX5IDX60X X X 0 IDX6
T0048-04
PCM1850A
PCM1851A
SLES173 MARCH 2006
The system reset control is used to resynchronize the system via the serial port when the system clock
frequency, interface mode, and data format are changed. Change them while SRST = LOW. If they are changed
during normal operation, analog performance can be degraded.
SRST SYSTEM RESET
0 Resynchronization
1 Normal operation (default)
The MRST bit is used to reset the mode control register to its default settings via the serial port.
MRST MODE REGISTER RESET
0 Set default value
1 Normal operation (default)
The user-programmable built-in functions of the PCM1850A can be controlled through a serial control port with
the SPI format. All operations for the serial control port use 16-bit data words. Figure 27 shows the control data
word format. The most-significant bit must be set to 0. Seven bits, labeled IDX[6:0], set the register index (or
address) for write operations. The least-significant eight bits, D[7:0], contain the data to be written to the register
specified by IDX[6:0].
Figure 28 shows the functional timing diagram for writing to the serial control port. MS (pin 30) is held at a logic-1
state until a register needs to be written. To start the register write cycle, MS is set to logic-0. Sixteen clocks are
then provided on MC (pin 31), corresponding to the 16 bits of the control data word on MD (pin 32). After the
sixteenth clock cycle has completed, the data is latched into the indexed mode control register in the write
operation. To write the next data word, MS must be set to 1 once.
Figure 27. Control Data Word Format for MD
Figure 28. Serial Control Format
23
Submit Documentation Feedback