Datasheet

LM5066
SNVS655G JUNE 2011REVISED FEBRUARY 2013
www.ti.com
Table 5. OT_FAULT_LIMIT Register
Value Meaning Default
0h – 0FFEh Overtemperature Fault threshold value 0960h (150°C)
0FFFh Overtemperature Fault detection disabled n/a
OT_WARN_LIMIT (51h)
The OT_WARN_LIMIT command is a standard PMBus command that allows configuring or reading the threshold
for the overtemperature warning detection. Reading and writing to this register should use the coefficients shown
in Table 41. Accesses to this command should use the PMBus read or write word protocol. If the measured
temperature exceeds this value, an Overtemperature warning is triggered and the OT WARN flags set in the
respective registers and the SMBA signal asserted. A single temperature measurement is an average of 16
round-robin cycles; therefore, the minimum temperature warn detection time is 16 ms.
Table 6. OT_WARN_LIMIT Register
Value Meaning Default
0h – 0FFEh Overtemperature Warn Threshold Value 07D0h (125°C)
0FFFh Overtemperature Warn detection disabled n/a
VIN_OV_WARN_LIMIT (57h)
The VIN_OV_WARN_LIMIT command is a standard PMBus command that allows configuring or reading the
threshold for the VIN over-voltage warning detection. Reading and writing to this register should use the
coefficients shown in Table 41. Accesses to this command should use the PMBus read or write word protocol. If
the measured value of VIN rises above the value in this register, VIN OV Warn flags are set in the respective
registers and the SMBA signal is asserted.
Table 7. VIN_OV_WARN_LIMIT Register
Value Meaning Default
0h – 0FFEh VIN Over-voltage Warning detection 0FFFh (disabled)
threshold
0FFFh VIN Over-voltage Warning disabled n/a
VIN_UV_WARN_LIMIT (58h)
The VIN_UV_WARN_LIMIT command is a standard PMBus command that allows configuring or reading the
threshold for the VIN under-voltage warning detection. Reading and writing to this register should use the
coefficients shown in Table 41. Accesses to this command should use the PMBus read or write word protocol. If
the measured value of VIN falls below the value in this register, VIN UV Warn flags are set in the respective
register, and the SMBA signal is asserted.
Table 8. VIN_UV_WARN_LIMIT Register
Value Meaning Default
1h – 0FFFh VIN Under-voltage Warning detection 0000h (disabled)
threshold
0000h VIN Under-voltage Warning disabled n/a
34 Submit Documentation Feedback Copyright © 2011–2013, Texas Instruments Incorporated
Product Folder Links: LM5066