Datasheet
Sliders
www.ti.com
4.7.7 V
OUT
4.5/5.0
The V
OUT
4.5/5.0 button programs bit 1 in Configuration Register 1. This changes the output voltage in
Voltage Output Mode to 5V when pushed or 4.5V when not pushed.
4.7.8 DisLL
The DisLL button gives the option of disabling the light load comparator of the LM3554 when pushed or
enabling the light load comparator when not pushed. When the light load comparator is disabled, the
LM3554 will not switch over to pulse skip mode at light load currents (typically I
OUT
= 100 mA with VIN =
3.6V). The light load comparator only applies when the LM3554 is operating in Voltage Out mode. In LED
mode the light load comparator is always disabled.
4.8 Shutdown Configuration Buttons
The following buttons correspond to Configuration Register 2, address (0xF0):
4.8.1 VIN Monitor SD
The VIN MONITOR SD button programs bit 3 of Configuration Register 2 with a ‘1’ when pushed, or a ‘0’
when not pushed. When this bit is a ‘1’, the LM3554 will be forced into shutdown when the VIN Monitor
feature is enabled (VIN Monitor Register bit [0] = 1), and the input voltage falls below the programmed VIN
Threshold. When this bit is a ‘0’, and the VIN Monitor feature is enabled, the LEDs are forced into Torch
mode when the input voltage falls below the programmed VIN Threshold.
4.8.2 Alt Ext Torch
When the Alt Ext Torch (Alternative External Torch) button is pushed, Configuration Register 2 bit 2 is
programmed with ‘1’. This sets the LM3554 up for Alternative External Torch mode (AET mode). In AET
mode the timeout counter is disabled when TX1 goes high before STROBE goes high. For example, in
AET mode a high on TX1, followed by a high on STROBE, forces the LEDs into Torch mode without a
timeout. If TX1 is then brought low with STROBE still high, the LEDs are forced into Flash mode, and the
timeout counter is re-enabled. When STROBE is brought low, or when the timeout counter expires, the
LEDs are turned off. When the Alt Ext Torch button is left un-pushed, this bit is programmed with a ‘0’,
and the LM3554’s timeout function operates normally.
4.8.3 NTC SD
When the NTC SD button is pushed, bit 1 of Configuration Register 2 is programmed with a ‘1’, and the
LM3554 is placed in NTC Shutdown mode. When the button is not pushed, bit 1 of Configuration Register
1 is programmed with ‘0’, and the LM3554 is placed into NTC force Torch mode. When the LM3554 is
placed in NTC mode (Configuration Register 1 bit 3 = 1), and NTC force shutdown mode, the LM3554 will
go into shutdown when the NTC voltage falls below 1.05V. When the LM3554 is placed in NTC mode
(Configuration Register 1 bit 3 = 1) and NTC force Torch mode, the LM3554 will reduce the active Flash
current to the programmed Torch level if the NTC voltage falls below 1.05V.
4.8.4 TX2 SD
When the TX2 SD button is pushed, Configuration Register 2 bit 0 is programmed with a ‘1’, and the
LM3554 is placed in TX2 Force Shutdown mode. If the LM3554 is placed into TX2 Force Shutdown mode,
and the ENVM/TX2 pin is configured as a TX2 input (Configuration Register 1, bit 5 = 1), a TX2 event
causes the LM3554’s LED current to turn off. If the LM3554 is placed into TX2 force Torch mode, and the
ENVM/TX2 pin is configured as a TX2 input (Configuration Register 1, bit 5 = 1), a TX2 event causes the
LM3554’s LED current to go from Flash mode to Torch mode.
A TX2 event is considered as a low-to-high transition at TX2 when the TX2 polarity bit is set for active
high (Configuration Register 1 bit 5 = 1) or a high-to-low transition on TX2 when the TX2 polarity bit is set
for active low (Configuration Register 1 bit 5 = 0).
8
AN-1742 LM3554 Evaluation Board SNVA646B–January 2009–Revised July 2013
Submit Documentation Feedback
Copyright © 2009–2013, Texas Instruments Incorporated