User Manual

Confidential
Manual Carrier Controller 2020-07-30
SPD6752150121R21_EN.docx Page 12 of 25
ATTENTION! Type 5 enclosure rating is only achieved when approved mating parts are used as
shown in the Approved mating parts table below
ATTENTION! Before connecting or disconnecting X109 the power must be switched off.
Motor hall sensor specification:
- 3 phase hall sensor interface
- +15V supply for hall sensors
- Hall sensor fault detection
- Resettable fuse
Table 3-17: Connector X109
Pin
I/O
Mnemonic
Description / Conditions
1
I
HALL_1
Hall phase 1 input (+15V)
2
I
HALL_2
Hall phase 2 input (+15V)
3
I
HALL_3
Hall phase 3 input (+15V)
4
PWR
VP_HALL+
Positive supply (+15V, 25mA)
5
PWR
GND
Negative hall supply
-
S
Shield
Shield for cable
Table 3-18: Approved mating parts X109
Manufacturer
Mfr. PN
Type
Description / Conditions
Remarks
Phoenix
1414148
Sealing cap
PROT-M12 MS-M
Finecables
BYD6.646.004
Motor
Hall sensor cable