8 Using the product 
14 
8.1.2  Automatic mode 
The manifold automatically detects the pressure difference between the low-
pressure and high-pressure sides. If the measured pressure on the low pressure 
side is 1 bar higher than on the high pressure side, a dialogue appears and the 
display can be changed accordingly. If “yes” is selected, the low pressure moves 
from left to right and the high pressure moves from right to left.  
This mode is particularly suitable for air conditioning systems that provide 
cooling and heating. 
8.2  Measuring mode 
 WARNING 
Risk of injury caused by refrigerant that is under high pressure, hot, cold, 
or toxic!
>
  Wear protective goggles and safety gloves. 
>
  Before applying pressure to the measuring instrument: Always fasten the 
measuring instrument on the suspension hook to prevent it from falling 
(danger of breakage). 
>
  Before each measurement, check the refrigerant hoses are intact and 
connected properly. Do not use any tools to connect the hoses; only tighten 
hoses hand-tight (max. torque 5.0 Nm/3.7 ft*lb). 
>
  Comply with the permissible measuring range (-1 to 60 bar/-14.7 to 870 
psi). 
Pay particular attention to this in systems with R744 refrigerant, since these 
are frequently operated at higher pressures! 
8.2.1  Refrigeration 
The Refrigeration application is used to determine the following system 
measuring values: 
•  High pressure 
•  Low pressure 
•  Refrigerant evaporating temperature 
•  Refrigerant condensation temperature 
•  Temperature of suction line 
•  Temperature of liquid line 