Data Sheet

Table Of Contents
8 Using the product
14
8.1.2 Automatic mode
The manifold automatically detects the pressure difference between the low-
pressure and high-pressure sides. If the measured pressure on the low pressure
side is 1 bar higher than on the high pressure side, a dialogue appears and the
display can be changed accordingly. If “yes” is selected, the low pressure moves
from left to right and the high pressure moves from right to left.
This mode is particularly suitable for air conditioning systems that provide
cooling and heating.
8.2 Measuring mode
WARNING
Risk of injury caused by refrigerant that is under high pressure, hot, cold,
or toxic!
>
Wear protective goggles and safety gloves.
>
Before applying pressure to the measuring instrument: Always fasten the
measuring instrument on the suspension hook to prevent it from falling
(danger of breakage).
>
Before each measurement, check the refrigerant hoses are intact and
connected properly. Do not use any tools to connect the hoses; only tighten
hoses hand-tight (max. torque 5.0 Nm/3.7 ft*lb).
>
Comply with the permissible measuring range (-1 to 60 bar/-14.7 to 870
psi).
Pay particular attention to this in systems with R744 refrigerant, since these
are frequently operated at higher pressures!
8.2.1 Refrigeration
The Refrigeration application is used to determine the following system
measuring values:
High pressure
Low pressure
Refrigerant evaporating temperature
Refrigerant condensation temperature
Temperature of suction line
Temperature of liquid line