5 Using the manifold
9
WARNING
Over tightening the valve stem shutoffs may cause:
Damage to the PTFE seal.
Mechanical deformation of the valve piston leading to the
PTFE seal falling out.
Damage to the thread of the threaded spindle and the valve
screw.
valve knobs to brake.
Lightly tighten the valve knob. Do not use tools to tighten the valve
stem shutoffs.
5 Using the manifold
5.1. Preparing for measurement
5.1.1. Switching the instrument On
> Press [ / ].
Zero the pressure sensors before every measurement.
All connections must be at ambient pressure.
> Press
[P=0] key for 3 seconds to execute zeroing.
Connecting the refrigerant hoses
Before each measurement check whether the refrigerant hoses are
in flawless condition.
Make sure the valve stem shutoffs are closed.
1. Connect the refrigerant hoses to the low-pressure side (blue)
and high-pressure side (red).
2. Connect the refrigerant hoses to the AC/R system.