User Manual

5 Using the manifold
14
- The display illumination will flash if:
The critical pressure of the refrigerant is within 15 psi (1 bar) of
the highest pressure (and temperature) where the refrigerant can
still condense
The maximum. permissible pressure of 870 psi (60 bar) is
exceeded.
Key functions for 550 or 549 when used with optional probes
> Press
[▲] or [▼] to change the reading in the display.
(The temperature probes must be connected.)
Possible display combinations:
Refrigerant evaporation
temperature Ev/to (°F/°C)
Evaporation pressure
(psi/bar)
Refrigerant condensation
temperature Co/tc (°F/°C)
Condensation pressure
(psi/bar)
Measured temperature T1/t
oh
(°F/°C)
Evaporation pressure
(psi/bar)
Measured temperature T2/t
cu
(°F/°C)
Condensation pressure
(psi/bar)
Superheating SH/Δt
oh
(°F/°C)
Evaporation pressure
(psi/bar)
Subcooling SC/Δt
cu
(°F/°C)
Condensation pressure
(psi/bar)
With both NTC temperature probes connected, Δt is also shown.
>
Press [Mean/Min/Max] to display min./max. readings and
mean values.
Changeable
- Evaporation
Temperature (Ev)
- Measured
Temperature (T1)
- Superheating (SH)
Changeable
- Condensation
Temperature (Co)
- Measured
Temperature (T2)
- Subcooling (SC)
Condensation
pressure
Evaporation
pressure