User's Manual

6 Technical data
18
6.1.2. General technical data
Feature
Values
Parameters
Pressure: psi / kPa / MPa / bar
Temperature: °F / °C / K
Vacuum: micron / inHg / inH
2
O / hPa / mbar /
mTorr /Torr / Pa
Sensors
2 Pressure: sensors, 2 Temperature (NTC
Thermistors)
Measuring cycle
0.5 s
Interfaces
Pressure connections: 3 x 1/4" SAE,
1x 3/8" SAE
NTC measurement
External vacuum probe
Measuring ranges
Pressure measurement range
HP/LP: -14.7…870 psi / -100…6000 kPa
/ -0.1…6 MPa / -1…60 bar (rel)
Temperature measurement
range: -58…302 °F / -50…+150 °C
Measurement range vacuum (abs):
0 … 20.000 micron
Overload
940 psi, 65 bar, 6500 kPa, 6.5 MPa
Resolution
Resolution pressure: 0.1 psi / 0.01 bar /
1 kPa / 0.001 MPa
Resolution temperature: 0.1 °F / 0.1 °C /
0.1 K
Vacuum resolution:
1 micron (from 0 to 1000 micron)
10 micron (from 1000 to 2000 micron)
100 micron (from 2000 to 5000 micron)
500 micron (from 5000 to 10000 micron)
5000 micron (from 10000 to 20.000 micron)
Accuracy (nominal
temperature 71.6 °F
/ 22 °C)
Pressure: ±0.5% FS (±1 digit)
Temperature: -58 to 302°F (0.9°F ± 1 digit) / -
50 to 150°C (±0.5 °C ±1 digit)
Vacuum: ±10% +10 micron
No. of refrigerants
60