User Manual

TSM400-4-CPTH_R1.0 August 2022 Page 5
8. Status indicator
The status of the device is shown by a single LED, located inside the box:
If the LED blinks for a period of 1 second, the sensor works properly;
If the LED blinks for a period of 3 seconds, there isn‘t communication with the controller;
If LED doesn‘t blink, there isn‘t a power supply.
9. Factory default settings
Disconnect the sensor from the bus (switch off the power supply).
Press and hold the “config” button. Don’t release the button, connecting the sensor to the bus
(switch on the power supply).
The “status” LED will be ON for 3 seconds and after this will flash for 7 seconds. After the 10-th
second the LED will be ON.
Release the button. The sensor will restart with factory default settings.
10. Firmware update
The firmware of the sensor can be updated with a Teracom controller which supports
MODBUS RTU or MBRTU-Config software. For more details ask your dealer.
11. Modbus address table
Register name
R/W
FC
Logical
Address
(Decimal)
Offset
(Decimal)
Data size
Default
Valid values
RS-485 address
R/W
03/06
40011
40001
16-bit uns. integer
1
1-247
Baud rate*
R/W
03/06
40012
40001
16-bit uns. integer
19200
2400, 4800, 9600,
19200, 38400, 57600
Parity, data, stop bits *
R/W
03/06
40013
40001
16-bit uns. integer
1
1=E81, 2=O81, 3=N81
Data order
R/W
03/06
40014
40001
16-bit uns. integer
1
1=MSWF (MSW, LSW)
2=LSWF (LSW, MSW)
Sub-family number
R
3
40015
40001
16-bit uns. integer
1
0xC9
FW version
R
3
40016
40001
16-bit uns. integer
Vendor URL
R
3
40017
40001
64 bytes UTF-8
teracomsystems.com
Float test value (MSWF)
R
3
40083
40001
32-bit float
-9.9(0xC11E6666)
Float test value (LSWF)
R
3
40085
40001
32-bit float
-9.9(0xC11E6666)
Signed integer test value
R
3
40087
40001
16-bit sig. integer
-999(0xFC19)
Signed integer test value
(MSWF)
R
3
40088
40001
32-bit sig. integer
-99999(0xFFFE7961)
Signed integer test value
(LSWF)
R
3
40090
40001
32-bit sig. integer
-99999(0xFFFE7961)
Unsigned integer test value
R
3
40092
40001
16-bit uns. integer
999(0x03E7)
Unsigned integer test value
(MSWF)
R
3
40093
40001
32-bit uns. integer
99999(0x0001869F)
Unsigned integer test value
(LSWF)
R
3
40095
40001
32-bit uns. integer
99999(0x0001869F)
Temperature °C
R
3
40101
40001
32-bit float
Humidity %RH
R
3
40103
40001
32-bit float
Dew point °C
R
3
40105
40001
32-bit float
CO
2
, ppm
R
3
40107
40001
32-bit float
Pressure, hPa
R
3
40109
40001
32-bit float
Temperature °C
R
3
40201
40001
32-bit float
Humidity %RH
R
3
40203
40001
32-bit float