Indoor Fireplace User Manual
31
TDVN Series Direct Vent Gas Fireplace
20007636
Manifold pressure can be measured by using a 5/16”
I.D. hose in the right hand side of the valve and con-
necting a manometer. Two test gauge ports are acces-
sible for test gauge connection:
1. Tap on left side of the valve will give inlet supply
pressure.
2. Tap on the right side of the valve will give manifold
pressure.
Min. Input Max. Input
33TDVP 13,000 18,000
36TDVP 14,500 20,000
39TDVP 16,500 22,000
FC107
SIT820
valve conversion
10/03
A
B
C
O
F
F
P
I
L
O
T
O
N
FC107
Fig. 49 Remove mounting screws, pressure regulator tower
and diaphragm assembly, and discard.
D
E
F
FC108
SIT
regulator
conversion
10/03
O
F
F
P
I
L
O
T
O
N
FC108
Fig. 50 Replace regulator.
Gas Supply Pressure (inches w.c.)
Minimum Normal Maximum
LP (Propane) 10.8 11.0 14.0
Manifold Pressure (inches w.c.)
Nornal (HI) Normal (Low)
LP (Propane) 10.0” 6.3”
Pressure ranges are: