User's Manual

56034903 © 2008 Telular Corporation
12
5.3.3 Disconnect Telguard from RJ-31x
Jack
Disconnect the Plug from J6 (Gray Connector) of the Telguard that goes to the RJ-31x Jack at the
premise.
5.3.4 Verify Alarm Signal Transmissions over Cellular
Trip several alarms on the C/C and verify that the central station received them by calling the central
station operator. Use a lineman's buttset in MONITOR MODE and connected to Telguard's "T" and "R"
test pins to "listen" to communications between the C/C and Telguard. The ACK LED will come on solid
while waiting for an acknowledgement.
If you are having problems getting reliable alarm signal transmissions, additional adjustments may be
necessary.
Recheck signal strength. You need RSSI = (TWO LEDS ON SOLID AND THE THIRD LED
FLASHING) for adequate signal strength. Also, check antenna connector and make sure it is seated
correctly.
Call Telular Technical Service, 1-800-229-2326 extension 9, and request the Communication
Center operator to check the Telguard programming configuration for proper operation and proper
communications format.
5.4 STEP 4: CONNECT SUPERVISORY TRIP OUTPUTS
Connect and test the supervisory trip outputs to the C/C.
NOTE: Activation of a local alarm or strobe light may be desirable when a trip is declared. The STC trip output
can be used directly to activate a local signaling device, provided that the trip output is not needed to trip the host
control/communicator at the same time. If both a local signal and a control trip input is required, then external
relays are needed to provide additional uncommitted contacts.
UL Listed installation of the TG-7 will at a minimum have the trip output (STC2) to the host C/C to indicate low
A/C (ACFC) and low battery (LBC) conditions.
5.4.1 Decide on a STC Trip Output Strategy
The Telguard provides the host C/C with two supervisory trip outputs for reporting a Telguard system
trouble code to the central station. The supervisory trip outputs are programmable via a touch-tone
telephone or buttset to suit various installation requirements. The programming options for these
supervisory trip outputs can be any combination of the following:
a. Always Off: Disables all relay supervisory functions.
b. ACFC: Trips 2-hours after loss of AC power. Restores 60 seconds after AC power is restored.
c. LBC: Trips within 60 seconds on low battery condition. Restores when battery voltage 12.1 vdc.
d. LFC: Trips 30/60-sec. on Telco line fault condition. Restores 30/60 seconds after Telco line restores.
e. NSC: Trips 30/60-sec. on no service condition due to loss of RF signal strength. Restores 30/60
seconds after RF signal strength is available.
f. RFC: Trips on radio failure to communicate with the Telular Communication Center
5.4.2 Check Telguard Supervisory Trip to C/C
After you have connected the STC trip outputs, check to be sure that they operate correctly.
5.4.2.1 Reprogram C/C to Send Proper Code
Reprogram C/C, if necessary, to send proper alarm code when tripped by the Telguard’s supervisory
output. Program zone restoral as desired.