User's Manual

56034903 © 2008 Telular Corporation
11
EXAMPLE
To change the Telguard factory default for STC 1 Trip Output reporting from only LFC to include all
system trouble conditions the installer would power down the Telguard, connect a butt-set to the T &
R test points, reconnect power.
Next press #, * the unit will generate 2 beeps.
Then press 850, the Telguard will respond with 2 beeps, then press 31, the Telguard will respond with 2
beeps, then press *, you will hear 2 beeps then hang up (this will change STC 1 trip output to report all
system trouble conditions). The Telguard will automatically transmit a message to update the Telular
Communication Center.
5.3.2 Complete the Telguard Programming Data Sheet
Fill out the following Telguard Programming Data Sheet. The completed data sheet enables you to
properly install and test the Telguard as well as provide a valuable aid to future troubleshooting if it
becomes necessary. Detach and retain this data sheet in your customer account file for future
reference. The Telguard default setup is pre-programmed at the factory. Default setup values are
listed and highlighted in "bold" type.
MEMORY
LOCATION
FIELD DEFAULT
VALUE
SETTING
831 Mode of operation 1 1 = Telco Primary/Cellular Backup
2 = Cellular Primary/Telco Backup
833 C/C Reporting Format 09 01= 4x2 pulse, 40pps 2300 hz 02= 4x2 pulse, 20pps 2300 hz
03= 4x2 pulse, 20pps 1400 hz 04= 3x1 pulse, 40pps, 2300 hz
05= 3x1 pulse, 20pps, 2300 hz 06= 3x1 pulse, 10pps, 1400 hz
07= Radionics IIe or IIIa
2
08 = Contact ID
09 = Auto Format Detect
11 = SIA2 (300 Baud) 12 = DMP
850 STC 1 Trip Output
Reporting
Normally Open
04 Enter the SUM TOTAL of the events that you wish to trip the
STC relay by ADDING the corresponding values:
00 = STC Trip Input Not Used
01 = AC Failure 04 = LFC 16 = RFC
02 = Low Battery 08 = NSC 31 = All
851 STC 2 Trip Output
Reporting
Normally Closed
27 Enter the SUM TOTAL of the events that you wish to trip the
STC relay by ADDING the corresponding values:
00 = STC Trip Input Not Used
01 = AC Failure 04 = LFC 16 = RFC
02 = Low Battery 08 = NSC 31 = All
852 STC Trip Delay for LFC
and NSC
2 1=30 seconds 2=60 Seconds 3= 3 minutes 4=10 minutes
5= 20 minutes 6=30 minutes 7=45 minutes 8=60 minutes
9= 24 hours
861 CFC Number of Events 0 0 = disabled 2 = 4 attempts
1 = 2 attempts 3 = 8 attempts
862 CFC between Events 1 1 = 30 seconds 3 = 70 seconds 5 = 90 seconds
2 = 60 seconds 4 = 80 seconds 6 = 99 seconds
872 AC Failure Delay 02 0-24 hours, default = 2 hours
899 Factory Default Unit