User's Manual

56034903 © 2008 Telular Corporation
4
The following supervisory features or combination of features are programmable to trip the STC
relays in order to meet a variety of installation requirements:
Trips on AC fail condition (ACFC)
Trips on low or missing battery condition (LBC).
Trips on line fault condition (LFC).
Trips on no service condition (NSC).
Trips on radio communication failure condition (RFC).
The following system trouble features are embedded in the Telguard for tripping the STC relay and
cannot be changed:
Tripped when unit is not registered with the Telular Communications Center (TCC)
Trips on catastrophic failure (CF) if all power is lost.
Trips on transmit-disable command from the Communication Center. This radio command
disables only the Telguard transmitter and would be used, for example, to shut down the
Telguard due to a runaway dialer.
2.7 D
IAGNOSTIC AND STATUS LEDS
Six LEDs are provided as a useful aid during installation and give installers an immediate visual indication of
system status.
LED Function Table – Normal Operating Mode (J10 = OUT)
LED Symbol Color Duty Cycle Indication
LED #1
Green
Solid On Unit is registered with the message center and enabled
Registration Off Unit not registered with message center (and disabled)
Flashing Unit is registered but disabled
LED #2
Red
Off ALL OK
STC 1 Flash* System Trouble Condition – Low/Missing AC Power
(System Trouble
Condition)
2 Flashes* System Trouble Condition – LBC or Battery Charger Failure
3 Flashes* System Trouble Condition – LFC
4 Flashes* System Trouble Condition – NSC
5 Flashes* System Trouble Condition – RFC
6 Flashes* System Trouble Condition – DTF
LED #3
MODE
Yellow
Off Mode 2, Cell Priority
On Mode 1, Telco Priority
Fast Flash C/C off-hook to transmit signals over cellular.
LED #4
Acknowledgement
Red
Solid On Telguard waiting for acknowledgement from Communication
Center
Off Idle state
Flashing When flashing with LED #1 unit has failed registration due to
the programming of the panel, CALL TECH SUPPORT
LED #5
Radio
Green
Off TG-7 initialized
On TG-7 initializing & registering with cellular network or
Transmitting Alarm Data
Short Flash (1 sec) Radio receiving message
Long Flash (2 sec) Radio sending message
LED #6
AC Power
Red Solid On AC power connected to unit