Installation Instructions
56025001 Page © 2003 Telular Corporation
13
5.3.1.1 Command Key Sequences for Pots Programming
Key Sequence Description
# * 0 * 1 2 3 4 4 3 2 1# Enters the programming Mode
On hook Exits programming and stores changes
The syntax for programming a specific memory location is as follows:
# * Memory location (3digits) *, value, #
For example, to change the Telguard factory default for STC 1 Trip Output reporting from all
system troubles to only to include LBC, the installer would power down the Telguard, connect a
buttset to the JP 5 connector, reconnect power,
Next press # * 0 * 1 2 3 4 4 3 2 1 #
Then press # * 850 * 2 #
And hang up this will change STC 1 trip output to report only LFC
5.3.3 Complete the Telguard Programming Data Sheet
Fill out the following Telguard Programming Data Sheet. The completed data sheet enables you to
properly install and test the Telguard as well as provide a valuable aid to future troubleshooting if it
becomes necessary. Detach and retain this data sheet in your customer account file for future reference.
The Telguard default setup is pre-programmed at the factory. Default setup values are listed and
highlighted in "bold" type.
Customer Name:
Telguard Serial No:
Installation Location:
Date Installed: Installed By:
MEM
LOC.
FIELD DEFAULT
VALUE
NEW PROGRAM
VALUE
SETTING
832
C/C Reporting Format
8 8 = Contact ID
850
STC 1 Trip Output Reporting
4
Enter the SUM TOTAL of the events that you wish to trip the STC relay
by ADDING the corresponding values:
(ex: 01+02+08+16=27) Note that a LFC will not trip the STC relay.
Program 31 (27+04) for all supervised features to trip the STC relay.
00 = STC Trip Input Not Used
01 = AC Failure 04 = LFC 16 = RFC
02 = Low Battery 08 = NSC 31 = All
851
STC 2 Trip Output Reporting
27 SAME AS ABOVE LOCATION 851
852
STC Trip Delay for LFC and NSC
2
1=30 Seconds 2=60 Seconds
861
CFC Number of Events
0
0 = disabled 2 = 4 attempts
1 = 2 attempts 3 = 8 attempts
862
CFC between Events
1 1 = 30 seconds
2 = 60 seconds
863
RFC Number of Attempts
3
0=Disabled 3 = 3 Attempts 6 = 6 Attempts
1=1 Attempts 4 = 4 Attempts 7 = 7 Attempts
2=2 Attempts 5 = 5 Attempts 8 = 8 Attempts
867
Standby Battery Size
(standard lead-acid battery)
4
0 = No Battery 3 = 4 ah
1 = 0.8 ah 4 = 7 ah
2= 1.2 ah 5 = 14 ah
899
Factory Default Unit