A4.0 UL Installation Requirements Summary Table
Household
Burglary
Household
Fire
Household
Burg/Fire
Combination
Central
Station
Burg
Grade B
Central
Station
Burg
Grade A
Police
Connect
Burg
Grade A
Bank,
Safe and
Vault
Grade A
Commercial
Fire
Commercial
Fire &
Central
Station Burg
Grade A
T200C001 T200C001 T200C001 T300C00
1
T300C00
1
T300C00
1
T300C00
1
T200C001
T300C001
Telguard Model Required.
O O O Y Y Y Y* O Y
UL Listed Bell and Bell
Housing **
O O O O O O Y Y Y
AC transformer lines in rigid
conduit.
Y Y Y Y Y Y Y Y Y
AC transformer plugged into
unswitched outlet.
O O O O O O Y Y Y
AC transformer plugged into
dedicated branch circuit.
O O O O O O Y Y Y
AC transformer enclosed in
Listed pull box (example:
Hoffman A-SG8x8x6).
- - - N N N N N N
PBX connection to RJ31X
jack.
O O O Y Y Y Y O Y
Enclosure Tamper Switch
connected to 24-hour circuit.
O O O O Y Y Y Y Y
Antenna cable in flexible
conduit concealed or covered
by motion detector.
O O O Y Y Y Y O Y
Attack resistant enclosure
(APC-32S).
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
72 hrs.
Use
14Ah.
24 hrs.
Use
7Ah.
24 hrs.
Use
7Ah.
12V. Battery backup
requirement.
*
Must be connected to C/C UL Listed for Bank and Vault
**
Use Mercantile Listed bell and bell housing