A3.4
(Must use Telguard Model T200C001 or Model T300C001 for Commercial Fire or Residential Fire
applications.)
A.
All cables between the host fire alarm control communicator and the Telguard must be enclosed in rigid
conduit and Host fire alarm C/C and Telguard must be within 3 feet of each other.
B.
Must be Listed fire alarm central station control or Listed combination fire/burglar alarm control unit
with two-line integral or Listed remote DACT installed according to manufacturer’s instructions.
C.
Antenna must be installed indoors in an area concealed from field of vision.
D.
Installations using conduit: (conduit only required for commercial fire applications)
1. Mount a Listed pull box (e.g., Notifier Integrated System, Model:NISCAB-4) as close to the
Telguard as possible. The pull box dimensions should not be less than 8”W x 8”H x 6”D.
2. Interconnect the pull box and Telguard with conduit and wire the Listed transformer (e.g., Revere,
P/N: RT-1620SL) to the Telguard in accordance with local wiring codes.
3. Plug the transformer into the 120 VAC receptacle and secure the transformer.
4. Secure the pull box cover.
5. AC power cable between the pull box housing and Telguard and between the host fire alarm control
communicator must be enclosed in rigid conduit.
E.
Direct Telco line connection required. No PBX.
A3.5.1 Supervisory Requirements for Listed Fire Configurations
Listed
Fire
Telguard
Supervisory
Trip to
Host
Telguard Programming Host C/C Programming
Configuration Trip Output C/C* Supervised
Condition
Setup
Requirement
Transmission
to Central
Station**
Local
Annunciation
LBC
LFC
Enabled
Enabled with
30 or 60-sec.
delay.
Yes
Yes
Optional
Yes***
NSC Enabled with
30 or 60-sec.
delay.
Yes Yes***
Telco Primary/
Radio Secondary
UL864/NFPA Fire
Alarm Central
Station Service.
(Telguard
switches)
STC Yes
AC Failure
RFC
CFC
DTF
(Self-Test)
Enabled
4 Attempts
4 Attempts
None
Monthly
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes***
* Trips must be 24-hour initiating circuits
** Use trouble code with restoral.
*** Must activate a trouble buzzer in the host C/C chassis and not the local bell/given.