User's Manual

56019201
Pag
e
© 2000 Telular Corporation
36
A3.4 UL864/NFPA F
IRE
A
LARM
C
ENTRAL
S
TATION
S
ERVICE
Installation and Wiring Requirements for UL commercial and residential fire usage to achieve
UL864/NFPA Fire Alarm Central Station Service
using Telguard model
T200C001
.
Refer to Appendix
A3.5 for “Note” explanations.
Telco Primary/Radio Secondary - Host C/C switches communication paths
TG2 ULE.VSD
HOST C/C
EARTH GROUND
TO DIGITAL DIALER
TO TELCO RJ31X
ZONE TRIP INPUT
INITIATION CIRCUITS:
See Appendix A3.5.1
J2
J1
NOTE
E
.
TELCO DIALER
PRI
SEC
PREMISE
PHONES
RJ31X
1234 67
STC (COM)
STC (N.O.)
+ BATTERY 12V
- BATTERY
5
PRIMARY
INCOMING
TELCO
AC (16.5V 40VA)
AC (16.5V 40VA)
BLANK PIN
16.5 VAC
20 VA
Transformer
NOTE
B
.
NOTE
D
.
NOTE
A
.
TRANSCEIVER
REMOTE ANTENNA
NOTE
C
.
TELGUARD
R