User's Manual
56019201
Pag
e
© 2000 Telular Corporation
30
A2.2 Telguard Communication Formats
Telguard Standard Communication Formats
NAME HANDSHAKE
FREQUENCY
DATA
FREQUENCY
BAUD RATE FORMAT EXTENDED KISS OFF
FREQUENCY
Telguard
CODE
RADIONICS (Double Round) 2300Hz 1800Hz 40 PPS 4-2 NO 2300Hz 1
FRANKLIN (Double Round) 2300Hz 1800Hz 20 PPS 4-2 NO 2300Hz 2
SIA P3 (Double Round) 1400Hz 1900Hz 20 PPS 4-2 NO 1400Hz 3
RADIONICS (Double Round) 2300Hz 1800Hz 40 PPS 3-1 NO 2300Hz 4
FRANKLIN (Double Round) 2300Hz 1800Hz 20 PPS 3-1 NO 2300Hz 5
SIA P1 (Double Round) 1400Hz 1900Hz 10 PPS 3-1 NO 1400Hz 6
Radionics Modem IIE or 3A
2
FSK 300 BPS 4 digits account FSK 7
ADEMCO CONTACT ID DUAL TONE
1400Hz / 2300Hz
DTMF DTMF 4-2-1-3-2-3 NO 1400Hz 8
A2.3 Compatible Control Communicators
For UL Listed Commercial Burglary and Fire, and Residential Burglary and Fire (Combination Listed)
Telguard Compatible Data Formats
1
Radionics
2
Franklin
3
SIA P3
4
Radionics
5
Franklin
6
SIA P1
7
Radionics
Modem
8
Ademco
C/C
Model
UL LISTED
4+2 40pps
2300Hz
ACK
4+2 20pps
2300Hz
ACK
4+2 20pps
1400Hz
ACK
3+1 40pps
2300Hz
ACK
3+1 20pps
2300Hz
ACK
3+1 10pps
1400Hz
ACK
IIE or 3A
2
Ademco
Contact ID
(DTMF)
DS7400Xi X X X X X X X
NAPCO MA3000 X X X X X X X
Radionics D2112 X X
Radionics D2212 X X
Radionics D4112 XX
Radionics D6112 XX
Radionics D7212 X
Radionics D7412 X
Radionics D8112 XX
Radionics D9112 X
Radionics D9412 X
A2.4 Compatible Receivers
Receiver
Compatible Data Formats
1
Radionics
2
Franklin
3
SIA P3
4
Radionics
5
Franklin
6
SIA P1
7
Radionics
Modem
8
Ademco
Model
UL LISTED
4+2 40pps
2300Hz ACK
4+2 20pps
2300Hz
ACK
4+2 20pps
1400Hz
ACK
3+1 40pps
2300Hz
ACK
3+1 20pps
2300Hz
ACK
3+1 10pps
1400Hz
ACK
IIE or 3A
2
Ademco
Contact ID
(DTMF)
FBI CP220 X X X X X X X
Radionics 6500 X X X X X X X
Osborne-Hoffman
Quickalert
X XXXXX X
Silent Knight 9000 X X X X X X X
SUR-GARD DRL2A X X X X X X X X
Ademco 685 X X X X X X X