User's Manual

56020801
Pag
e
© 2000 Telular Corporation
17
5.3 S
TEP
3: T
RANSMIT
C/C A
LARMS OVER THE
C
ELLULAR
R
ADIO
N
ETWORK
Confirm that the Telguard enables the host C/C to transmit alarm signals over the cellular radio network. In checking
this, do not connect the incoming telco line to the Telguard or connect the supervisory trip output (STC) to the C/C
zone input.
5.3.1 Connect C/C to Telguard
Jack 2
Unplug the modular jack of the C/C-to-RJ31X cable (not supplied) from the RJ31X and plug it into
J2 on the Telguard.
NOTE: Since no RJ31X telco cable is connected to J1 at this point in the installation, the
Telguard is detecting a telco line fault condition (LFC). The Telguard is forced to
switch transmission paths from telco to cellular causing all C/C alarm signals to be
transmitted over the cellular radio network during testing in this step.
TG3 Step 03.VSD
HOST C/C
24 HOUR ZONE COMMON
24 HOUR ZONE INPUT
TELCO DIALER
DETAILS ON JACK AND PIN ASSIGNMENTS,
TERMINAL STRIP, JUMPER, AND STATUS LEDS.
SEE APPENDICES A1.1 THROUGH A1.4 FOR
J2
FUSE 3A 3AG
T
R
1234
56
STC (COM)
STC (N.O.)
+ BATTERY 12V
- BATTERY
7
AC (16.5V 40VA)
AC (16.5V 40VA)
BLANK PIN
J1
EARTH G ROUND
R
ANTENNA
TRANSCEIVER
RJ31X
PREMISE
PHONES
INCOMING
TELCO
TELGUARD
LED MODE SELECT
J5
IN = RSSI
OUT = NORMAL
SIGNAL
STRENGTH
LEDS
AC POWER
SYSTEM TROUBLE
RADIO TX
OPERATION MODE
STATUS LEDS
(See Appendix A1.3)