FOREWORD
A word about the significance of our UL Listings: These UL Listings allow the Telguard
models to meet certain
requirements of insurance companies, fire marshals, building inspectors and other regulatory authorities in burglary
and fire alarm service as follows:
1. In Burglary Alarm Service
: When used in conjunction with a Listed central station burglary alarm control unit
with integral or Listed DACT that is connected to a Listed Grade A bell and bell housing, the combined
control/communicator and Telguard T300C001 is suitable for Grade A central station service. This is one grade
higher than a Listed control/communicator can obtain on its own without some type of external line supervision,
such as is involved in UL AA service.
A UL Grade A Listing is available in installations where the host Listed burglary alarm control/communicator
transmits through the T300C001 solely on cellular ("Cellular only": No Telco; Cellular primary). Also, where
the control/communicator is switched to transmit over cellular when it can not reach the central station over telco
("Cellular backup for Telco": Telco primary; Cellular secondary).
The specific UL Listings for the T300C001 with respect to burglary alarm service are Residential Burglary,
UL1023. Central Station Burglar Alarm Systems, UL1610; Police Station Connected Alarm Systems, UL365; and
Digital Alarm Communicators, UL1635.
2. In Fire Alarm Service:
When used in conjunction with a Listed central station fire alarm control unit with a two-
telco line integral or Listed DACT, the combined control/communicator and Telguard T200C001 meet the
requirements for commercial fire alarm usage under UL 864 and NFPA. This enables the T200C001 to be the
second "phone line" in commercial fire installations.
In UL/NFPA Listed fire alarm installations, the Listed two-line fire alarm control communicator must always use
telco as the primary transmission path, switching to cellular only when and if it can not reach the central station
over telco. Also, the T200C001 may be employed in residential fire, UL985 applications.
Appendices A3.1 through A3.3.1 (burglary alarm service) and A3.4 through A3.5.1 (fire alarm service) show the
installation configurations and the connections that must be made to meet various UL Listing requirements.