User's Manual

Appendix A
Calibrate the Analog Output to 5.0V
Equipment Needed: Voltmeter
Set voltmeter to DC Voltage.
On J5, measure between Pin 1 (Orange) and Pin 5 (White).
Change thermostat mode to OFF.
Enter Advanced Command 35 01 and press ON/OFF.
Enter Advanced Command 36 36 and press ON/OFF.
This should cause your reading to go close to 5.0V.
Change the value of 36 36 up or down a few values so it reads close to 5.0V. If you have to raise it
more than 36 50 or lower than 36 25, then there is an issue. Contact engineering
Enter Advanced Command 35 00
Verify that in the OFF mode, output is approx. 0.0V.
EcoWave Featuring EcoTouch IO&M Guide Telkonet, Inc.
For Use with Firmware Version 2.x 20800 Swenson Drive, Suite 175
Appendix A Waukesha, WI 53186
Revision 2 (800) 380-9640
Page 40 www.telkonet.com