User's Manual

EcoSense+ IOM Guide
Telkonet, Inc.
For Use With Firmware V. 2.x
20800 Swenson Drive, Suite 175
Maintenance
Waukesha, WI 53186
Revision
2
(800) 380-9640
Page 8
www.telkonet.com
Step 4 Using
2 x 50lb EZ-Anchors with screws, m
ount
the EcoSense+ backplate into the wall or
ceiling.
AimthePIR*IMPORTANTSTEP*
Step 5 Insert the angle set screwdriver into the set
screw.
Step 6 Rotate the set screw which in turn rotates
the PIR sensor to the desired position. Use
the Current Position Indicator as your
guide. See Figure 1 PIR Rotation Design.
Step 7 Replace cover by lining up the backplate
with the cover and gently twisting it
clockwise until it is seated correctly.
Step 8 Insert the security screw and tighten.
JoinandBind
Step 9 Join the EcoSense+ to the network and bind
it to the thermostat. See Device
Association Guide for instructions.
Maintenance
ReplacingtheBatteries
Estimated battery life is 6 years.
Batteries are monitored by the network. You will
be notified when to replace them. For non-
networked installations, the “Service Sensor” will
light up when it is time to change the battery.
Standard alkaline batteries are
recommended for use in EcoSense+
sensors. Lithium-Ion, Nickel-Cadmium, or
other specialized batteries may not
provide acceptable long-term
performance.
Step 1 Remove the security screw from the
EcoSense+.
Step 2 Disconnect the EcoSense+ cover from the
back plate by twisting the cover counter-
clockwise and lifting the cover out of the
back plate.
Step 3 Disconnect the thermostat communication
wires from the green dry contact
connector, if any.
Step 4 Remove the batteries.
Step 5 Verify the battery terminals are clear of
oxidation and battery acid.
Step 6 Insert the replacement batteries.
Step 7 Verify the batteries are firmly in place.
Step 8 Reconnect the thermostat communication
wires coming from the wall to the green
dry contact connector, if necessary.
Step 9 Align the EcoSense+ cover with the
backplate.
Step 10 Reconnect the face of the EcoSense+ to the
backplate by placing it inside the
backplate, then twisting the face clockwise
until it is secure.
Step Reinsert and tighten the security screw on
the EcoSense+.
If the device must be removed, always
reinstall in the same location and the
same position.