Maintenance Menu
Table 6: Maintenance Menu Functions
Menu Item Function
Learn Used to associate the SS6010 to other EcoSmart wireless devices in the room, such as an
EcoSense, EcoContact, EcoGuard, or EcoSwitch. For step-by-step instructions on associating
devices, see EcoSmart Firmware 2.x Device Association Guide.
Erase Will tell the SS6010 to forget all of the wireless devices it has been associated with, such as an
EcoSense, EcoContact, EcoGuard or EcoSwitch. The large number shown in the Erase menu
indicates the number of devices currently associated with the SS6010. Press On/Off to erase all
associated devices.
Signal Advanced command, which should only be changed with the assistance of Telkonet.
Recovery Sets the value for the number of minutes for Recovery Time. The number displayed indicates
the current recovery time, and can be incremented using the up or down arrows. Setting a
value of zero (0) will disable the energy manage set back feature.
Setpoint
MAX
Indicates the current maximum temperature that a user can set. Can be incremented by using
the up and down arrows. This value must be lower than the MAX Setback.
Setpoint
MIN
Indicates the current minimum temperature that a user can set. Can be incremented by using
the up and down arrows. This value must be higher than the MIN Setback.
MAX
Setback
Indicates the maximum temperature a room can reach, either through guest setting or an
unoccupied drift.
MIN Setback Indicates the minimum temperature a room can reach, either through guest setting or an
unoccupied drift.
Calibration Allows authorized personnel to calibrate the ambient temperature to ensure accurate readings.
Mesh The Mesh submenu contains advanced commands for adjusting the ZigBee mesh network. These
options should only be changed with the assistance of Telkonet.
Stat ID This is an advanced command, which should only be changed with the assistance of Telkonet.
Time Allows authorized personnel to set the time on the thermostat.
Schedule If Schedules are in use, allows authorized personnel to select a schedule for the thermostat to
use.
Adv Prog This section contains multiple advanced commands that can be run on the SS6010. For details
on what Advanced Commands are available, please contact your Telkonet Project Manager or
Technical Support for a command list.