Regular Maintenance
Procedure: Visual Inspection
Step 1 Verify that components have not been tampered with, destroyed or stolen.
Step 2 Verify that the components are securely mounted on their respective surfaces.
Sensors may be mounted on walls or ceilings; either location is permissible and will have been
determined during installation.
Step 3 If applicable, verify that the AC power is being supplied to the HVAC system.
Step 4 If units are hard-wired, verify that the power/data wiring between the SS6010 and the
EcoSense are intact and connected.
Step 5 Check for a Service icon on the SS6010 display. This icon indicates loss of association with
one or more sensors.
Step 6 If the icon appears, first check the batteries. Replace batteries if necessary.
Step 7 If batteries are not the cause of the Service icon, erase and re-associate all sensors per
instructions in the EcoSmart Firmware 2.x Device Association Guide.
Procedure: Functional Inspection
Step 1 Observe whether the HVAC system is operating (e.g. drive cycle) after entering the room.
In most cases, entering the room will have initiated an HVAC drive cycle after the Sensor detected
occupancy. Possible exceptions:
-If the temperature in the room is within hysteresis of the HVAC setpoint, a drive cycle may not
commence
-A delay may have been programmed into the SS6010 thermostat, instructing the unit to wait for a
particular duration before triggering a drive. (Although uncommon, this feature is sometimes
requested by a property. In almost all cases, the delay is less than 3 minutes.)
Step 2 If a drive cycle does not initiate within 5 minutes of entry, force a drive cycle by
temporarily setting the thermostat to some arbitrary high or low temperature (ensure the
HVAC mode is set correctly).
SS6010 thermostats default to Occupied status if communication with the SS6010 or sensor(s) is lost
for any reason. This permits the units to continue to maintain the room temperature. However, in
this state energy savings will be lost. If in doubt whether the sensors are associated, re-associate all
Sensors per the EcoSmart Firmware 2.x Device Association Guide.