Beta ( 0 to 50 degrees C ) = 3892 degrees K nominal
Other models may be compatible; provide model number and specifications.
Analog Outputs
See Appendix B
CT Inputs
All Models have 2 inputs. The CT inputs are commonly used for monitoring/alerting on fan motors, compressors
or other equipment with excessive load or for determining a failure. The CT Inputs must be used with a
compatible CT and sized appropriately for the load they will be connected to.
Current Transformer (CT) approved models from Sentran Corp.:
Rated loads are 100, 50, 30, 20 and 10 A respectively.
BCF-100A: 0.025A
LCF-50A: 0.025A
LCF-30A:0.025A
LCF-20A:0.025A
LCF-10A: 0.01A
Preferred operating range is between 10 and 80% of rated load.
Other models may be compatible: provide model number and specifications
If not sized correctly the CT may damage the thermostat.