User's Manual

Add-Ons
EcoInsight+ SS6010
I, O & M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
Add-Ons
Waukesha, WI 53186
Revision 2.1
(800) 380-9640
Page 22 www.telkonet.com
Add-Ons
About Wiring
The SS6010 interconnects with the existing HVAC system via standard wiring conventions, using 24-277VAC OR
24VDC voltage supplied by the HVAC system itself.
Note: The SS6010 does not allow three different power sources, as the SS6600 does. On the SS6010, all three
poles must be connected to the same power source.
The SS6010 does not support wiring directly, as the SS6600 does. Instead, we provide bare leads. It is up to the
installer to connect these leads using an appropriate method described herein. Wiring conventions follow
industry standards; however, it is important to note that the relay configuration is dynamic and can be
modified at the factory or in the field. It is important to always follow site-specific wire diagrams.
Relay Configuration
The thermostat comes with a default relay configuration, which sets the functions of each pin. This default can
be changed to one of several alternate relay configurations, which are stored in the memory of the thermostat.
To change your thermostat relay configuration, see Maintenance Menu
Table 6, specifically command #2.
Speed Configurations
The SS6010 will ship with a default speed configuration that matches the default relay configuration. The
speed configuration controls the timing of shifts between both fan speeds and stages of HVAC for compressor
based systems. The speed configuration will have a 3 minute safety delay between compressor cycles and upon
power up. The SS6010 also has several alternative embedded speed configurations. See Maintenance Menu
Table 6: Maintenance Menu Functions, specifically command #3.
NTC Probe
Temp probes can be used for multiple purposes:
1. HVAC Discharge Air temp
2. HVAC Return Air temp
3. Supply Water Temp
4. AquaStat Mode (switches thermostat’s Heat/Cool)
For temperature probe if not using Telkonet provided external temperature probe, a probe with a Beta R0 must
match. Alternatively, a probe can be provided to Telkonet for lab calibration. Required specifications:
US Sensor model USP10972 or equivalent, per the following:
Resistance at 25 degrees C = 10 000 ohms +/- 1%
Resistance/Temperature curve = "J"