38. Slowly bring the left side toward the wall as shown. Use care not to force the faceplate
closed. If you encounter resistance, make sure no wires are pinched between components and
that no pins are bent.
39. Once the thermostat has been snapped onto the back plate, use a hex wrench to insert the
safety screw in the location shown in Figure 10: Thermostat Side View on page 17.
40. Remove all lockouts or tags from the circuit breaker.
41. Return the electrical circuit to operation.
42. Verify the SS6010 thermostat display is active.
43. Test all components to make sure that you can engage both the heat and air conditioning,
and all supported fan settings (high, low, etc.). Wiring is complete.
44. Join, pair and bind. (See Device Association Guide for details.)
Rating Schedule– Class 2:
INPUTS:
Input Type (i.e. Supply, Sensor,
Communication)
Terminals
Input Rating
Communication J8, J9, J10, J11
3.3 Vdc max. Class 2, SELV, Low Power (Less than 15
watts)
Accessible communications: RS232 J12 5 Vdc max.
Class 2, SELV, Low Power (Less than 15
watts)
Power Supply J3-1 (R) and J3-
2 (C)
24 Vac/Vdc (Nominal); 30 Vac/Vdc max. Class 2, SELV,
Low Power (Less than 15 watts)