19. Strip the LINE wire back 0.25 inches.
20. Cap the LINE wire with a wire nut or electrical tape.
21. Cut the COMMON wire so the copper is flush with the insulation.
22. Strip all wires except for COMMON back 0.25 inches.
23. Determine which end of the adapter should be situated on top, and which end should be
situated on the bottom.
24. Mount the Telkonet JBOX adapter plate to the mud ring with two #6-32 1” screws.
25. Mount SS600 backplate on top of JBOX adapter plate, using four #5 ½” coarse thread screws.
26. Connect each Molex wire to the matching functional wire within the JBOX. Refer to
27. . (If controlling proportional valve or ECM fan, see Appendix B.) Any unused wires must be
capped according to NEC standards.
For variable output connections, see Appendix B on page 35.
28. Connect all other wires and harnesses as per the tables in the Tables section, which begins on
page 30.
29. Mount SS6010 backplate on top of JBOX adapter plate, using four #5 ½” coarse thread screws
30. Feed wire harnesses through the applicable holes in the backplate. High and low voltage
wires must be fed through separate holes as shown in Figure 7 (on page 11).
31. Connect the harnesses to the SS6010.
32. Ensure backplate has appropriate jumpers between R, SW1 and SW2. If installing on a head
pump, ensure there is a jumper between Y1 and W1.
33. Ensure no airflow from the JBOX or wall cavity is able to seep into the thermostat through the
wire harness. Telkonet recommends the use of approved UL caulk or UL rated insulating tape
to avoid false temperature readings. Figure 8 (page 12) illustrates sections of insulating tape
on the backplate, covering the wall opening.
34. Continue to Step 35 (on page 19).
Steps Common to all Installation Methods
35. Connect all Molex harnesses.
36. Hook the thermostat to the hinges on the right side of the backplate.
37. Line up the hinges on the thermostat to the notches on the backplate. Press the right side of
the thermostat tightly against the back plate.