User's Manual
Low Voltage Installation (Class 2)
EcoInsight+ SS6010
I, O & M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
Low Voltage Installation (Class 2)
Waukesha, WI 53186
Revision 2.1
(800) 380-9640
Page 18 www.telkonet.com
5. Separate the back plate from the thermostat: Use a flathead screwdriver to GENTLY press the
tab next to the screw hole to allow the thermostat to pop open. WARNING: Using too much
force can break the tab.
For drywall mounting instructions, see below.
For JBOX vertical installation instructions, go to page 18
For JBOX horizontal installation instructions, go to page
Drywall Mounting Instructions
Requires four 50 lb. EZ-Lock anchors and provided screws
6. Strip the LINE wire back 0.25 inches.
7. Cap the LINE wire with a wire nut or electrical tape.
8. Cut the COMMON wire so the copper is flush with the insulation.
9. Strip all wires except for COMMON back 0.25 inches.
10. Verify the wiring now looks similar to Figure 11.
Figure 11: Drywall Mount Wiring
11. Ensure the wiring Molex has appropriate wires jumped between R, SW1 and SW2 (assuming
they are controlling all fan and modes from the same voltage as powering the thermostat). If
installing on a heat pump, ensure that Y1 and W1 are jumped together.
12. Connect wires and harnesses as per the tables in the Tables section, which begins on page 30.
13. Verify each wire is secure by gently tugging on it.
14. Hold backplate against wall at appropriate height. Using a pen, level-mark your 4 holes.
15. Use appropriate drill for anchor and insert anchors into holes.
16. Screw backplate to the wall and into the anchors. Re-check that it is still level.
17. Connect the harnesses to the SS6010.
18. Continue to Step 35 (on page 19).
JBOX Using Vertical Mud Ring Instructions
Requires Telkonet JBOX Adapter Plate and two #6-32 1” screws