User's Manual

High Voltage Installation (Non-Class 2)
EcoInsight+ SS6010
I, O & M Guide
Telkonet, Inc.
For Use with Firmware Version 2.x
20800 Swenson Drive, Suite 175
High Voltage Installation (Non-Class 2)
Waukesha, WI 53186
Revision 2.1
(800) 380-9640
Page 15
www.telkonet.com
interrupts one pole of the supply circuit. Accordingly, the thermostat/relay is restricted to controlling fixed
electric space heating loads with a single ungrounded conductor – such as loads connected to a 120 or 277 Vac
circuit.
Note 3: The total connected load of Relays 5, 7 and 8 should not exceed 16 Amps (through common terminal
J3-9).
Note 4: Wiring to J3 must exit the enclosure at Opening A of the backplate as shown in Figure 6 and Figure 7
(page11). Wiring to all other connectors must exit the enclosure at Opening B of the backplate. Class 2 and
Non-Class 2 wiring must not be mixed within a junction box or conduit run.