6.70.104 SS2000 / SS2200 Association Procedures 5/2010
3. After approximately 30 seconds, the LED will indicate the relative signal strength as
red, yellow, or green. Yellow or Green are acceptable levels. If a red signal is shown,
relocate the sensor to a better location.
4. Poke the 1107. The sensor LED will now blink to indicate the number of sensors
which are associated to it. This blinking is normal, and allows an easy way for
maintenance personnel to verify that the sensor(s) are still communicating to the
controller.
Figure 1: SS1107 ports, indicators, and controls
Sensor Dissociation, SS1107
To force the SS1107 to drop sensor associations, follow these steps:
1. Press and hold the SS1107 microswitch for approximately 10 seconds.
2. The LED will double-blink red for 8-10 seconds while the switch is pressed, then go
blank.
3. Once the LED is dark, all previously sensor associations will be deleted.
Note that you cannot dissociate a single sensor from among multiples – all sensor association is
dropped when the above process is invoked. You will need to re-associate any desired sensors.